963, Jalan Perusahaan, Kawasan Perindustrian Prai, 13600 Prai, Pulau Pinang, Malaysia.
Malaysia | Thailand | Singapore-Indonesia | Vietnam | Philippines
The PSU-Series is a single output programmable switching DC power supply covering a power range up to 1520W. This Series of products include five models with the combination from 6V to 60V rated voltages. As th ePSU-series can be connected in series for maximum 2 units or in parallel for maximum 4 units, capacity of connecting multiple PSU-Series units for higher voltage or higher current output provides a broad coverage of applications.
PSU-Series Specifications
The specifications apply when the PSU-Series is powered on for at least 30 minutes under +20°C~+30°C.
Output |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Rated Output Voltage (*1) |
|
V |
6 |
12.5 |
20 |
40 |
60 |
Rated Output Current (*2) |
|
A |
200 |
120 |
76 |
38 |
25 |
Rated Output Power |
|
W |
1200 |
1500 |
1520 |
1520 |
1500 |
Constant Voltage Mode |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Line regulation (*3) |
|
mV |
2.6 |
3.25 |
4 |
6 |
8 |
Load regulation (*4) |
|
mV |
2.6 |
3.25 |
4 |
6 |
8 |
Ripple and noise (*5) |
p-p (*6) |
mV |
60 |
60 |
60 |
60 |
60 |
|
r.m.s. (*7) |
mV |
8 |
8 |
8 |
8 |
8 |
Temperature coefficient |
|
ppm/ °C |
100ppm/°C of rated output voltage, after a 30 minute warm-up. |
||||
Remote sense compensation voltage (single wire) |
|
V |
1 |
1 |
1 |
2 |
3 |
Rise time (*8) |
Rated load |
ms |
80 |
80 |
80 |
80 |
80 |
|
No load |
ms |
80 |
80 |
80 |
80 |
80 |
Fall time (*9) |
Rated load |
ms |
10 |
50 |
50 |
80 |
80 |
|
No load |
ms |
500 |
700 |
800 |
1000 |
1100 |
Transient response time (*10) |
|
ms |
1.5 |
1 |
1 |
1 |
1 |
Constant Current Mode |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Line regulation (*3) |
|
mA |
22 |
14 |
9.6 |
5.8 |
4.5 |
Load regulation (*11) |
|
mA |
45 |
29 |
20.2 |
12.6 |
10 |
Ripple and noise (*12) |
r.m.s. |
mA |
400 |
240 |
152 |
95 |
75 |
Temperature coefficient |
|
ppm/ °C |
100ppm/°C of rated output voltage, after a 30 minute warm-up. |
||||
Protection Function |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Over voltage protection (OVP) |
Setting range |
V |
0.6-6.6 |
1.25-13.75 |
2-22 |
4-44 |
5-66 |
|
Setting accuracy |
V |
0.06 |
0.125 |
0.2 |
0.4 |
0.6 |
Over current protection (OCP) |
Setting range |
A |
5-220 |
5-132 |
5-83.6 |
3.8-41.8 |
2.5-27.5 |
|
Setting accuracy |
A |
4 |
2.4 |
1.52 |
0.76 |
0.5 |
Under voltage limit (UVL) |
Setting range |
|
0-6.3 |
0-13.12 |
0-21 |
0-42 |
0-63 |
Over temperature protection (OHP) |
Operation |
|
Turn the output off. |
||||
Incorrect sensing connection protection (SENSE) |
Operation |
|
Turn the output off. |
||||
Low AC input protection (AC-FAIL) |
Operation |
|
Turn the output off. |
||||
Shutdown (SD) |
Operation |
|
Turn the output off. |
||||
Power limit (POWER LIMIT) |
Operation |
|
Over power limit. |
||||
|
Value (fixed) |
|
Approx. 105% of rated output power |
||||
Analog Programming and Monitoring |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
External voltage control output voltage |
|
|
Turn the output off. |
||||
External voltage control output current |
|
|
Turn the output off. |
||||
External resistor control output voltage |
|
|
Turn the output off. |
||||
External resistor control output current |
|
|
Turn the output off. |
||||
Output voltage monitor |
|
|
Turn the output off. |
||||
Output current monitor |
|
|
Turn the output off. |
||||
Shutdown control |
|
|
Turns the output off with a LOW (0V to 0.5V) or short-circuit. |
||||
Output on/off control |
|
|
Possible logic selections: |
||||
Alarm clear control |
|
|
Clear alarms with a LOW (0V to 0.5V) or short-circuit. |
||||
CV/CC/ALM/PWR ON/OUT ON indicator |
|
|
Photocoupler open collector output; Maximum voltage 30V, maximum sink current 8mA. |
||||
Trigger out |
|
|
Maximum low level output = 0.8V; minimum high level output = 2V; Maximum source current = 8mA. |
||||
Trigger in |
|
|
Maximum low level input voltage = 0.8V; minimum high level input votage = 2.0V, Maximum sink current = 8mA. |
||||
Front Panel |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Display, 4 digits |
|
|
|
|
|
|
|
Voltage accuracy |
0.1% + |
mV |
12 |
25 |
40 |
80 |
120 |
Current accuracy |
0.2% + |
mA |
600 |
360 |
228 |
114 |
75 |
Indications |
|
|
GREEN LED's: CV, CC, V, A, VSR, ISR, DLY, RMT, LAN, M1, M2, M3, RUN, Output ON |
||||
Buttons |
|
|
Lock/Local(Unlock), PROT(ALM_CLR), Function(M1), Test(M2), Set(M3), Shift, Output |
||||
Knobs |
|
|
Voltage, Current |
||||
USB port |
|
|
Type A USB connector |
||||
Programming and Measurement (RS-232/485, USB, LAN, GPIB) |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Output voltage programming accuracy |
0.05% + |
mV |
3 |
6.25 |
10 |
20 |
30 |
Output current programming accuracy |
0.2% + |
mA |
200 |
120 |
76 |
38 |
25 |
Output voltage programming resolution |
|
mV |
0.2 |
0.4 |
0.7 |
1.3 |
2 |
Output current programming resolution |
|
mA |
6 |
4 |
2.5 |
1.2 |
0.8 |
Output voltage measurement accuracy |
0.1% + |
mV |
6 |
12.5 |
20 |
40 |
60 |
Output current measurement accuracy |
0.2% + |
mA |
400 |
240 |
152 |
76 |
50 |
Output voltage measurement resolution |
|
mV |
0.2 |
0.4 |
0.7 |
1.3 |
2 |
Output current measurement resolution |
|
mA |
6 |
4 |
2.5 |
1.2 |
0.8 |
Input Characteristics |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Norminal input rating |
|
|
100Vac to 240Vac, 50Hz to 60Hz, single phase |
||||
Input voltage range |
|
|
85Vac ~ 265Vac |
||||
Input frequency range |
|
|
47Hz ~ 63Hz |
||||
Maximum input current |
100Vac |
A |
21 |
||||
|
200Vac |
A |
11 |
||||
Inrush current |
|
|
Less than 50A. |
||||
Maximum input power |
|
VA |
2000 |
||||
Power factor |
100Vac |
|
0.99 |
||||
|
200Vac |
|
0.98 |
||||
Efficiency (*13) |
100Vac |
|
77 |
82 |
83 |
84 |
84 |
|
200Vac |
|
79 |
85 |
86 |
87 |
87 |
Hold-up time |
|
|
20ms or greater |
||||
Interface Capabilities |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
USB |
|
|
TypeA: Host, TypeB: Slave, Speed: 1.1/2.0, USB Class: CDC(Communications Device Class) |
||||
LAN |
|
|
MAC Address, DNS IP Address, User Password, Gateway IP Address, Instrument IP Address, Subnet Mask |
||||
GPIB |
|
|
SCPI - 1993, IEEE 488.2 compliant interface |
||||
RS-232/RS-485 |
|
|
Complies with EIA232D / EIA485 Specifications |
||||
Environment Conditions |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Operating temperature |
|
|
0˚C to 50˚C |
||||
Storage temperature |
|
|
-25˚C to 70˚C |
||||
Operating humidity |
|
|
20% to 85% RH; No condensation |
||||
Storage humidity |
|
|
90% RH or less; No condensation |
||||
Altitude |
|
|
Maximum 2000m |
||||
Environment Conditions |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Weight |
main unit only |
kg |
Less than 8.7kg |
||||
Dimensions |
(W×H×D) |
mm3 |
423×43.6×447.2 |
||||
Cooling |
|
|
Forced air cooling by internal fan. |
||||
EMC |
|
|
Complies with the European EMC directive 2004 /108/EC for Class A test and measurement products. |
||||
Safety |
|
|
Complies with the European Low Voltage Directive 2006 /95/EC and carries the CE-marking. |
||||
Withstand voltage |
|
|
AC to Chassis: 1500Vac/1min |
||||
Insulation resistance |
|
|
Chassis and output terminal; chassis and AC input; AC input and output terminal: 100MΩ or more (DC 500V) |
||||
|
|
|
|
|
|
|
|